mbusScanStop (Function)

Top  Previous  Next

Architecture:

NX32L

Firmware version:

1.94.00


This function is used to stop an M-Bus scan started with mbusScan.

 

 

Input:

handle : SYSHANDLE

A handle to the connection to stop scanning on.

 

Returns: INT

1

- Success

0

- Not supported

-1

- Invalid handle

-9

- Communication error

 

Declaration:

FUNCTION mbusScanStop : INT;
VAR_INPUT
   handle   : SYSHANDLE;
END_VAR;

 

 

Example:

INCLUDE rtcu.inc
 
FUNCTION CALLBACK OnScan;
VAR_INPUT
   handle      : SYSHANDLE;
   secondary   : STRING;
   primary     : INT;
END_VAR;
   DebugFmt(message:="device found: \1: "+secondaryv1:=primary);
END_FUNCTION;
 
FUNCTION CALLBACK OnProgress;
VAR_INPUT
   handle      : SYSHANDLE;
   secondary   : STRING;
   primary     : INT;
END_VAR;
   DebugFmt(message:="scanning: \1: "+secondaryv1:=primary);
END_FUNCTION;
 
PROGRAM test;
VAR
   mb : SYSHANDLE;
   rc : INT;
END_VAR;
 
   ...
   // Open wired M-Bus interface
   rc := mbusOpen(handle := mb);
   ...
   // Start scan for any secondary address
   rc := mbusScan(handle:=mbcb_found:=@OnScancb_progress:=@OnProgresssmode:=2mask:="FFFFFFFFFFFFFFFF");
   DebugFmt(message:="mbusScan(): \1", v1:=rc);
BEGIN
 
   ...
END;
END_PROGRAM;